B.5 E: Motor Parameters
u

E1: V/f Pattern for Motor 1

No.
(Addr.
Name
Hex)
E1-01
Input Voltage Setting
(0300)
E1-03
V/f Pattern Selection
(0302)
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
LCD Display
This parameter must be set to the power supply voltage.
WARNING! Electrical Shock Hazard. Drive input voltage
(not motor voltage) must be set in E1-01 for the protective
Input Voltage
features of the drive to function properly. Failure to do so
may result in equipment damage and/or death or
personal injury.
0: 50 Hz, Constant torque 1
1: 60 Hz, Constant torque 2
V/F Selection
2: 60 Hz, Constant torque 3 (50 Hz base)
0: 50 Hz
3: 72 Hz, Constant torque 4 (60 Hz base)
1: 60 Hz Saturation
4: 50 Hz, Variable torque 1
2: 50 Hz Saturation
5: 50 Hz, Variable torque 2
3: 72 Hz
6: 60 Hz, Variable torque 1
4: 50 Hz VT1
7: 60 Hz, Variable torque 2
5: 50 Hz VT2
8: 50 Hz, High starting torque 1
6: 60 Hz VT1
9: 50 Hz, High starting torque 2
7: 60 Hz VT2
A: 60 Hz, High starting torque 3
8: 50 Hz HST1
B: 60 Hz, High starting torque 4
9: 50 Hz HST2
C: 90 Hz (60 Hz base)
A: 60 Hz HST1
D: 120 Hz (60 Hz base)
B: 60 Hz HST2
E: 180 Hz (60 Hz base)
C: 90 Hz
F: Custom V/f, E1-04 through E1-13 settings define the V/f
D: 120 Hz
pattern
E: 180 Hz
F: Custom V/F
Note:
Description
Setting F is only available in vector control
modes.
B.5 E: Motor Parameters
Values
Page
Default: 230 V
<1>
147
Min.: 155
<1>
Max.: 255
<2>
Default: F
148
Range: 0 to 9;
A to F
271
B

Hide quick links:

Advertisement

Table of Contents
loading