5.2 Fault Detection
Digital Operator Display
Cause
There is phase loss in the drive input power
There is loose wiring in the drive input power
terminals
There is excessive fluctuation in the drive
input power voltage
There is poor balance between voltage phases Stabilize drive input power or disable phase loss detection.
The main circuit capacitors are worn
Digital Operator Display
Digital Operator Display
Cause
The proper braking resistor option has not
been installed
A regenerative converter, regenerative unit, or
braking unit is being used and the ⊕1 or ⊕3
terminal is connected to ⊖ terminal
Cause
Deceleration time is too short and excessive
regenerative energy is flowing back into the
drive
The duty cycle is too high
Excessive braking inertia
The braking operation duty cycle is too high
The proper braking resistor has not been
installed
Note:
The magnitude of the braking load trips the braking resistor overheat alarm, NOT the surface temperature. Using the braking resistor more
frequently than its rating permits will trip the alarm even when the braking resistor surface is not very hot.
Digital Operator Display
192
Input Phase Loss
PF
Drive input power has an open phase or has a large imbalance of voltage between phases. Detected when
L8-05 is set 1 (enabled).
• Check for wiring errors in the main circuit drive input power.
• Correct the wiring.
• Ensure the terminals are tightened properly.
• Apply the tightening torque as specified in this manual.
Tightening Torques on page 94
• Check the voltage from the drive input power.
• Review the possible solutions for stabilizing the drive input power.
• Check the maintenance time for the capacitors (U4-05).
• Replace the main capacitor(s) if U4-05 is greater than 90%. For instructions on replacing the
capacitor(s), contact Yaskawa or a Yaskawa representative.
Check for problems with the drive input power. If drive input power appears normal but the alarm
continues to occur, replace either the control board or the entire drive. For instructions on replacing the
control board, contact Yaskawa or a Yaskawa representative.
PG Disconnect (for any control modes using a PG option card)
PGo
No PG pulses are received for longer than the time set to F1-14.
PG Hardware Fault (detected when using a PG-X3 option card)
PGoH
PG cable is not connected properly.
Braking Resistor Fault
rF
The resistance of the braking resistor is too low.
Select a braking resistor option that it fits the drive braking transistor specification.
Set L8-55 to 0 to disable the braking transistor protection selection.
Braking Resistor Overheat
rH
Braking resistor protection was triggered.
Fault detection is enabled when L8-01 = 1 (disabled as a default).
• Check the load, deceleration time, and speed.
• Reduce the load inertia.
• Increase the deceleration times (C1-01 to C1-08).
• Replace the dynamic braking option with a larger device that can handle the power that is discharged.
Check the duty cycle. Maximum of 3% duty cycle is available when L8-01 = 1.
Recalculate braking load and braking power. Reduce the braking load by adjusting braking resistor
settings.
Check the braking operation duty cycle. Braking resistor protection for ERF-type braking resistors
(L8-01 = 1) allows a braking duty cycle of maximum 3%.
• Check the specifications and conditions for the braking resistor device.
• Select the optimal braking resistor.
Dynamic Braking Transistor
rr
The built-in dynamic braking transistor failed.
Fault Name
Possible Solution
for details.
Fault Name
Fault Name
Possible Solution
Possible Solution
Fault Name
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide