No.
(Addr.
Name
Hex)
F6-23
MECHATROLINK
(036E)
Monitor Selection (E)
F6-24
MECHATROLINK
(036F)
Monitor Selection (F)
Operation Selection at
F6-25
MECHATROLINK
(03C9)
Watchdog Timer Error
(E5)
F6-26
MECHATROLINK
(03CA)
bUS Errors Detected
F6-30
PROFIBUS-DP Node
(03CB)
Address
F6-31
PROFIBUS-DP Clear
(03CC)
Mode Selection
F6-32
PROFIBUS-DP Data
(03CD)
Format Selection
F6-35
CANopen Node ID
(03D0)
Selection
F6-36
CANopen
(03D1)
Communication Speed
F6-40
CompoNet Node
(03D5)
Address
F6-41
CompoNet
(03D6)
Communication Speed
F6-45
(02FB) BACnet Node Address BAC Node Address
F6-46
BACnet Baud Rate
(02FC)
F6-47
Rx to Tx Wait Time
(02FD)
F6-48
BACnet Device Object
(02FE)
Identifier 0
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
LCD Display
Mon E register
Sets the MECHATROLINK monitor (E).
Mon F register
Sets the MECHATROLINK monitor (F).
SI-T WDTErr Sel
0: Ramp to stop. Decelerate using the deceleration time in C1-02.
0: Ramp to Stop
1: Coast to stop
1: Coast to Stop
2: Fast stop. Decelerate using the deceleration time in C1-09.
2: Fast-Stop
3: Alarm only
3: Alarm Only
Num of SI-T BUS
Sets the number of option communication errors (bUS).
Sets the node address.
PB Node Address
PB Clear Select
0: Resets drive operation with a Clear mode command.
0: Reset to Zero
1: Maintains the previous operation state when Clear mode
1: Hold Prev Value
command is given.
PB Map Select
0: PPO Type
0: PPO Type
1: Conventional
1: Conventional
2: PPO (w/bit 0)
2: PPO (bit0)
3: PPO Type (Auto Enter)
3: PPO (Enter)
4: Conventional (Auto Enter)
4: Conv (Enter)
5: PPO (w/bit0, Auto Enter)
5: PPO (bit0,Enter)
Sets the node address.
CO Node Address
CO Baud Rate
0: Auto-detection
0: Auto Detect
1: 10 kbps
1: 10 kbps
2: 20 kbps
2: 20 kbps
3: 50 kbps
3: 50 kbps
4: 125 kbps
4: 125 kbps
5: 250 kbps
5: 250 kbps
6: 500 kbps
6: 500 kbps
7: 800 kbps
7: 800 kbps
8: 1 Mbps
8: 1Mbps
Reserved.
CN Node Adress
Reserved.
CN Baud Rate
Sets BACnet physical node address.
BAC Baud Rate
0: 1200
0: 1200 bps
1: 2400
1: 2400 bps
2: 4800
2: 4800 bps
3: 9600
3: 9600 bps
4: 19200
4: 19.2 kbps
5: 38400
5: 38.4 kbps
6: 57600
6: 57.6 kbps
7: 76800
7: 76.8 kbps
8: 115200
8: 115.2 kbps
Sets the wait time between receiving and sending for BACnet. Default: 5 ms
Rx to Tx Wait T
Sets the least significant word for BACnet.
BAC Dev Obj Id 0
Description
B.6 F: Option Settings
Values
Page
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
Default: 1
Range: 0 to 3
Default: 2
Min.: 2
Max.: 10
Default: 0
Min.: 0
Max.: 125
Default: 0
Range: 0, 1
Default: 0
Range: 0 to 5
Default: 0
Min.: 0
Max.: 126
Default: 6
Range: 0 to 8
Default: 1
Min.: 0
Max.: 127
Default: 3
Range: 0 to 8
Min.: 5
Max.: 65
Default: 0
Min.: 0
Max.: FFFF