5.6 F: Option Settings
F5-09: DO-A3 Output Mode Selection
Determines how the DO-A3 option card works with the drive.
No.
F5-09
Setting 0: Separate output functions for each of 8 terminals
Setting 1: Binary output
Setting 2: Output functions assigned by F5-01 through F5-08

◆ F6: Communication Option Card

These parameters configure communication option cards and communication fault detection methods.
F6-01: Operation Selection after Communications Error
Determines drive operation when a communication error occurs.
No.
F6-01
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only (continue operation)
F6-02: External Fault from Communication Option Detection Selection
Determines the detection method of an external fault (EF0) initiated by a communication option card.
No.
F6-02
Setting 0: Always detected
Setting 1: Detection during run only
F6-03: External Fault from Communication Option Operation Selection
Determines drive operation when an external fault is initiated by a communication option (EF0).
No.
F6-03
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only (continue operation)
F6-04: bUS Error Detection Time
Sets the delay time for bUS error detection.
No.
F6-04
182
Parameter Name
DO-A3 Output Mode Selection
Parameter Name
Operation Selection after Communications Error
Parameter Name
External Fault from Communication Option Detection Selection
Parameter Name
External Fault from Communication Option Operation Selection
Parameter Name
bUS Error Detection Time
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Setting Range
Default
0 to 2
Setting Range
0 to 3
Setting Range
0 or 1
Setting Range
0 to 3
Setting Range
0.0 to 5.0 s
0
Default
1
Default
0
Default
1
Default
2.0 s