Figure 5.31
10 V
Output Voltage
5 V
0 V
0%
Example 3: Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.
Figure 5.32
■
H4-07, H4-08: Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
No.
H4-07
H4-08
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
◆ H5: MEMOBUS/Modbus Serial Communication
Serial communication is possible in the drive using the built-in RS-422/485 port (terminals R+, R-, S+, S-) and
programmable logic controllers (PLCs) or similar devices running the MEMOBUS/Modbus protocol.
The H5-
parameters are used to set up the drive for MEMOBUS/Modbus Communications. Refer to
Modbus Communications on page 383
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
H4-07, 08 = 0
Gain 150%
Bias 0%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
100%
Monitor Value
Figure 5.31 Analog Output Gain and Bias Setting Example 1 and 2
Figure 5.32 Analog Output Gain and Bias Setting Example 3
Name
Terminal FM Signal Level Selection
Terminal AM Signal Level Selection
for detailed descriptions of the H5-
5.7 H: Terminal Functions
H4-07, 08 = 1
15 V
Output Voltage
10 V
5 V
-100%
100%
Monitor Value
-5 V
-10 V
-15 V
Setting Range
0 or 1
0 or 1
parameters.
common_TMonly
Gain = 150%
Bias = 0%
Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%
Default
0
0
MEMOBUS/
5
201