5.6 F: Option Settings

◆ F3: Digital Input Card Settings

These parameters set up the drive for operation with the option card DI-A3. Refer to the instruction manual packaged
with the option card for specific details on installation, wiring, input signal level selection, and parameter setup.
F3-01: DI-A3 Option Card Input Selection
Determines the type of input for digital option card DI-A3 when o1-03 is set to 0 or 1.
No.
F3-01
Setting 0: BCD, 1% units
Setting 1: BCD, 0.1% units
Setting 2: BCD, 0.01% units
Setting 3: BCD, 1 Hz units
Setting 4: BCD, 0.1 Hz units
Setting 5: BCD, 0.01 Hz units
Setting 6: BCD, special setting (5 digit input), 0.02 Hz units
Setting 7: Binary
Note: BCD input when o1-03 = 2 or 3. Units are determined by o1-03.
F3-03: DI-A3 Option Card Data Length Selection
Determines the number of bits for the option card input that sets the speed reference.
No.
F3-03
Setting 0: 8 bit
Setting 1: 12 bit
Setting 2: 16 bit
◆ F4: Analog Monitor Card Settings
These parameters set up the drive for operation with the analog output option card AO-A3. Refer to the instruction
manual packaged with the option card for specific details on installation, wiring, input signal level selection, and
parameter setup.
F4-01, F4-03: Terminal V1, V2 Function Selection
Selects the data to output from analog terminal V1. Enter the final three digits of U -
data is output from the option card. Some monitors are only available in certain control modes.
No.
F4-01
F4-03
F4-02, F4-04, F4-05, F4-06: Terminal V1, V2 Gain and Bias
Parameters F4-02 and F4-04 determine the gain, while parameters F4-05 and F4-06 set the bias. These parameters are set
as a percentage of the output signal from V1 and V2 where 100% equals 10 V output. The terminal output voltage is
limited to 10 V.
180
Parameter Name
DI-A3 Option Card Input Selection
Parameter Name
DI-A3 Option Card Data Length Selection
Parameter Name
Terminal V1 Function Selection
Terminal V2 Function Selection
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Setting Range
0 to 7
Setting Range
0 to 2
to determine which monitor
Setting Range
Default
000 to 999
000 to 999
Default
0
Default
2
102