S5-13: Direct Landing Minimum Speed Level
Sets the speed level for the start of Direct Landing. Direct Landing is disabled if the starting speed for Direct Landing is
less than the maximum output speed multiplied by this parameter (E1-04 × S5-13).
No.
S5-13

◆ S6: Faults for Elevator Applications

S6-01: Motor Contactor Response Error (SE1) Detection/Reset Selection
Determines when the drive should detect a motor contactor response error (SE1). SE1 is triggered if there is no response
from the motor contactor within the time set in S6-10 after the contactor control output has been set.
No.
S6-01
Motor Contactor Response Error (SE1) Detection/Reset Selection
0: Detect during stop, SE1 must be manually reset
1: Detect during stop, SE1 can be automatically reset
2: No SE1 detection
S6-02: Starting Current Error (SE2) Detection Delay Time
Sets a delay time for starting current error (SE2). SE2 is detected when the drive output current is below 25% after the
Up/Down command has been entered and the brake release time and the time set to S6-02 have both passed. The brake
control command will not be issued (brake stays applied).
No.
S6-02
S6-04: Output Current Error (SE3) Detection Delay Time
Sets a delay time for detecting an output current fault (SE3). SE3 is detected when the drive output current drops below
25% after the brake has released.
No.
S6-04
S6-05: Brake Response Error (SE4) Detection Time
Sets a delay time for detecting a brake response error (SE4). SE4 is detected when an output terminal set for "Brake
release" (H2-
= 50) and an input terminal set for "Brake feedback" (H1-
No.
S6-05
S6-10: Overacceleration Detection Level
If the elevator car accelerates at an abnormal rate, the drive triggers an overacceleration fault (dv6) and the motor coasts
to stop. Parameter S6-10 determines the acceleration rate that triggers the dv6 fault. A setting of 0.0 m/s
overacceleration detection.
No.
S6-10
<1> Default setting is determined by parameter o1-03. If o1-03 is set to 0 through 5, the default is 1.5 m/s
s
2
(setting range: 0.0 to 50.0 ft/s
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Parameter Name
Direct Landing Minimum Speed Level
Parameter Name
Parameter Name
Starting Current Error (SE2) Detection Delay Time
Parameter Name
Output Current Error (SE3) Detection Delay Time
Parameter Name
Brake Response Error (SE4) Detection Time
Parameter Name
Overacceleration Detection Level
2
).
5.11 S: Elevator Parameters
Setting Range
0 to 100%
Setting Range
0 to 2
Setting Range
0.00 to [S1-04 - S1-06]
Setting Range
0 to 5000 ms
= 79) do match for the time set to S6-05.
Setting Range
0 to 10000 ms
2
disables
Setting Range
0.0 to 20.0 m/s
2
2
. If o1-03 is set to 6, the default is 5.0 ft/
Default
20%
Default
0
Default
200 ms
Default
200 ms
5
Default
500 ms
Default
1.5 m/s
2
<1>
245