C.8 Message Examples

◆ Writing to Multiple Registers

Function code 10H allows the user to write multiple drive MEMOBUS/Modbus registers with one message. This process
works similar to reading registers, in that the address of the first register to be written and the data quantity are set in the
command message. The data to be written must be consecutive so that the register addresses are in order, starting from the
specified address in the command message. The data order must be high byte then lower byte.
The following table shows an example of a message where a forward (Up) operation has been set with a speed reference
of 100% for the slave 1 drive.
If parameter values are changed using the Write command, an Enter command may be necessary to activate or save the
data depending on the setting of H5-11.
Refer to Enter Command on page 408
Command Message
Slave Address
Function Code
Upper
Starting No.
Lower
Upper
Data Quantity
Lower
Number of Bytes
Upper
Starting Data
Lower
Upper
Next Data
Lower
Upper
CRC-16
Lower
Note: Double the number of the data quantity for the number of bytes in the command message.
396
Refer to H5-11: Communications Enter Function Selection on page 390
for detailed descriptions.
Response Message (normal)
01H
Slave Address
10H
Function Code
00H
Starting No.
01H
00H
Data Quantity
02H
04H
CRC-16
00H
01H
02H
58H
63H
39H
01H
Slave Address
10H
Function Code
Upper
00H
Error Code
Lower
01H
CRC-16
Upper
00H
Lower
02H
Upper
10H
Lower
08H
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Response Message (fault)
01H
90H
02H
Upper
CDH
Lower
C1H
and