5.10 o: Operator Related Settings

5.10 o: Operator Related Settings
These parameters control the various functions, features, and display of the digital operator.
◆ o1: Digital Operator Display Selection
These parameters determine the data display on the digital operator.
o1-01: Drive Mode Unit Monitor Selection
When the drive is powered up, the monitor selected in parameter o1-02 appears first on the display. If o1-02 is set to 5,
o1-01 can be used to change the content of this monitor.
When using an LED operator, pressing the up arrow key will display the following data: speed reference → rotational
direction → output speed → output current → o1-01 selection.
Parameter o1-01 selects the content of the last monitor in this sequence. There is no effect like this on an LCD operator.
No.
o1-01
<1> U2-
and U3-
parameters cannot be selected.
o1-02: User Monitor Selection after Power Up
Selects which monitor parameter is displayed upon power up. This is done by entering the 1
monitors are not available in some control modes.
No.
o1-02
Setting 1: Speed reference (U1-01)
Setting 2: Motor direction
Setting 3: Output speed (U1-02)
Setting 4: Output current (U1-03)
Setting 5: User-selected monitor (set by o1-01)
o1-03: Digital Operator Display Unit Selection
Sets the units used to display speed related settings and monitors as well as accel/decel rate settings and jerk settings.
Refer to
Digital Operator Display Unit Selection on page
No.
o1-03
Setting 0: 0.01 Hz units
Setting 1: 0.01% units (100% = max. output frequency)
Setting 2: r/min units (calculated by the max output frequency and the no. of motor poles)
Setting 3: User-set units (use o1-10, o1-11)
Set o1-03 to 3 for user-set units, then set parameters o1-10 and o1-11.
Set the value use for the maximum frequency reference to o1-10. The placement of the decimal point in this number
should be set to o1-11.
For example, to have the maximum output speed displayed as "100.00", set the o1-10 = 1000 and o1-11 = 2 (i.e., 1000
with 2 decimal points).
224
Name
Drive Mode Unit Monitor Selection
Refer to U: Monitor Parameters on page 247
Name
User Monitor Selection after Power Up
Name
Digital Operator Display Unit Selection
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Setting Range
U1-04 (Control Mode) to
U6-99 (Option Monitor 20)
Setting Range
99.
Setting Range
Default
105 to 699
106 (U1-06)
<1>
part of U1-
for a list of monitors.
Default
1 to 5
Default
0 to 6
. Certain
1
1