S5: Short Floor Operation - YASKAWA L1000A Technical Manual

Ac drive for elevator applications; type: cimr-luxa; 200 v class: 3.7 to 110 kw (5 to 150 hp); 400 v class: 3.7 to 132 kw (5 to 200 hp) a
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

5.11 S: Elevator Parameters

◆ S5: Short Floor Operation

Short Floor Function
Short Floor automatically adjusts the speed in order to reduce the leveling time if leveling speed was activated before the
selected speed was reached. Short Floor is enabled setting S5-01 = 1. The drive calculates the distance to decelerate from
rated speed to the leveling speed, then controls the stop so that the stopping time is shortened. In
Figure 5.45
below, area
S indicates the distance for a stop from nominal speed.
Figure 5.45
Speed
d1-19 (nominal speed)
S
nominal speed × 0.4
d1-26 (leveling speed)
0
t
Figure 5.45 Speed During Normal Operation
Advance Short Floor
Advanced Short Floor minimizes the operation time to arrive at a designated floor. It uses the leveling speed once the
leveling speed command is entered via one of the multi-function inputs (H1-
= 53). Advance Short Floor calculates
optimal speed based on the Short Floor Minimum Constant Speed Time (S5-03) and the currently selected deceleration
rate.
Table 5.14
explains how Short Floor and Advanced Short Floor work.
5
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
239