Fault Reset Methods - YASKAWA L1000A Technical Manual

Ac drive for elevator applications; type: cimr-luxa; 200 v class: 3.7 to 110 kw (5 to 150 hp); 400 v class: 3.7 to 132 kw (5 to 200 hp) a
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

6.8 Diagnosing and Resetting Faults

◆ Fault Reset Methods

When a fault occurs, the cause of the fault must be removed and the drive must be restarted. The table below lists the
different ways to restart the drive.
After the Fault Occurs
Fix the cause of the fault, restart the drive, and
reset the fault
Resetting via Fault Reset Digital Input S4
If the above methods do not reset the fault, turn off the drive main power supply. Reapply power after the digital
operator display is out.
Note: If the Up/Down command is present, the drive will disregard any attempts to reset the fault. Remove the Up/Down command
before attempting to clear a fault situation.
284
Procedure
Press
on the digital operator.
Close then open the fault signal digital input via terminal S4.
S4 is set for "Fault Reset" as default (H1-04 = 14).
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
ALARM
YEA_
DIGITAL OPERATOR JVOP-180
- MODE -
DRV
oC
Overcurrent
RESET
FWD
F1
F2
RESET
LO
ESC
RE
RESET
ENTER
RUN
STOP
Drive
Fault Reset Switch
S4 Fault Reset Digital Input
SC Digital Input Common
ON
2
OFF
1