A.4 Drive Watt Loss Data
Model Number
CIMR-L
2A0018
2A0025
2A0033
2A0047
2A0060
2A0075
2A0085
2A0115
2A0145
2A0180
2A0215
2A0283
2A0346
2A0415
<1> These values assume the carrier frequency is set to 5 kHz.
<2> These values assume the carrier frequency is set to 2 kHz.
Model Number
CIMR-L
4A0009
4A0015
4A0018
4A0024
4A0031
4A0039
4A0045
4A0060
4A0075
4A0091
4A0112
4A0150
4A0180
4A0216
4A0260
<1> These values assume the carrier frequency is set to 5 kHz.
<2> These values assume the carrier frequency is set to 2 kHz.
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Table A.3 Watt Loss 200 V Class Three-Phase Models
Rated Amps (A)
Heatsink Loss (W)
17.5
25.0
33.0
47.0
60.0
75.0
85.0
115.0
145.0
<1>
180.0
<1>
215.0
<1>
283.0
<1>
346.0
<2>
415.0
<2>
Table A.4 Watt Loss 400 V Class Three-Phase Models
Rated Amps (A)
Heatsink Loss (W)
9.2
14.8
18.0
24.0
31.0
39.0
45.0
60.0
75.0
91.0
112.0
<1>
150.0
<1>
180.0
<1>
216.0
<1>
260.0
<2>
Carrier Frequency 8 kHz
Interior Unit Loss (W)
100.7
67.4
194.4
92.3
213.8
104.8
280.2
129.9
394.9
162.8
459.8
220.9
510.3
210.9
662.4
250.0
815.9
306.3
976.0
378.1
1514.0
466.1
1936.2
587.8
2563.9
782.9
2672.1
954.1
Carrier Frequency 8 kHz
Interior Unit Loss (W)
68.5
61.0
135.4
85.7
149.9
97.0
208.0
115.1
262.6
140.8
329.8
179.4
348.5
169.6
484.1
217.2
563.4
254.0
722.6
299.0
908.2
416.4
1340.3
580.1
1771.4
541.0
2360.2
715.1
2390.9
786.7
A.4 Drive Watt Loss Data
Total Loss (W)
168.1
286.6
318.7
410.2
557.7
680.7
721.2
912.4
1122.2
1354.1
1980.2
2523.9
3346.8
3626.2
Total Loss (W)
129.5
221.1
246.9
323.2
403.4
509.2
518.1
701.3
817.4
1021.7
1324.6
1920.3
2312.5
3075.3
3177.6
A