C.4 Memobus/Modbus Setup Parameters - YASKAWA L1000A Technical Manual

Ac drive for elevator applications; type: cimr-luxa; 200 v class: 3.7 to 110 kw (5 to 150 hp); 400 v class: 3.7 to 132 kw (5 to 200 hp) a
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

C.4 MEMOBUS/Modbus Setup Parameters

C.4 MEMOBUS/Modbus Setup Parameters
◆ MEMOBUS/Modbus Serial Communication
This section describes parameters necessary to set up MEMOBUS/Modbus communications.
H5-01: Drive Slave Address
Sets the drive slave address used for MEMOBUS/Modbus communications.
Note: Cycle the power after changing this parameter to enable the new setting.
No.
H5-01
<1> If the address is set to 0, no response will be provided during communications.
Each slave drive must be assigned a unique slave address for serial communications to work. Setting H5-01 to any value
besides 0 assigns the drive its address in the network. Slave addresses do not need to be assigned in sequential order, but
no two drives may share the same address.
H5-02: Communication Speed Selection
Sets the MEMOBUS/Modbus communications speed.
Note: Cycle the power after changing this parameter to enable the new setting.
No.
H5-02
H5-02
0
1
2
3
4
H5-03: Communication Parity Selection
Sets the parity used for MEMOBUS/Modbus communications.
Note: Cycle the power after changing this parameter to enable the new setting.
No.
H5-03
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
H5-04: Stopping Method after Communication Error
Selects the stopping method after a communications error (CE) has occurred.
No.
H5-04
Setting 0: Ramp to stop (uses the deceleration ramp currently enabled)
Setting 1: Fast Stop (uses the deceleration ramp in C1-09)
Setting 2: Coast to stop
Setting 3: Alarm only (continue operation)
388
Name
Drive Slave Address
Name
Communication Speed Selection
Communication Speed
1200 bps
2400 bps
4800 bps
9600 bps
19200 bps
Name
Communication Parity Selection
Name
Stopping Method after Communication Error
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Setting Range
0 to FFH
<1>
Setting Range
0 to 5
H5-02
Communication Speed
5
6
7
8
Setting Range
0 to 2
Setting Range
0 to 3
Default
1FH
Default
3
38400 bps
57600 bps
76800 bps
115200 bps
Default
0
Default
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents