5.8 L: Protection Functions
Figure 5.33
L1-13: Continuous Electrothermal Operation Selection
Determines whether to hold the current value of the electrothermal motor protection (L1-01) when the power supply is
interrupted.
No.
L1-13
Setting 0: Disabled
Setting 1: Enabled

◆ L2: Undervoltage Detection

L2-05: Undervoltage Detection Level (Uv)
Determines the voltage at which a Uv1 fault is triggered. This setting rarely needs to be changed.
No.
L2-05
<1>
<1> Values shown are specific to 200 V class drives; double the values for 400 V class drives.
Note: Install an AC reactor option on the input side of the power supply when setting L2-05 below the default value to prevent damage
to drive circuitry.
◆ L3: Stall Prevention
When the load is too heavy or acceleration ramps are too short, the motor may be unable to keep up with the speed
reference, resulting in excessive slip. During acceleration, this usually causes an overcurrent fault (oC), drive overload
(oL2), or motor overload (oL1). The drive can prevent the motor from stalling and still reach the desired speed without
the user needing to change the acceleration or deceleration ramp settings. The Stall Prevention function can be set
separately for acceleration, operating at constant speeds, and deceleration.
L3-01: Stall Prevention Selection during Acceleration
Stall Prevention during acceleration (L3-01) prevents tripping with overcurrent (oC), motor overload (oL1), or drive
overload (oL2) faults common when accelerating with heavy loads.
L3-01 determines the type of Stall Prevention the drive should used during acceleration.
No.
L3-01
204
Operation time (minutes)
10
7
3
1
0.4
0.1
0
100
Figure 5.33 Motor Protection Operation Time
Name
Continuous Electrothermal Operation Selection
Name
Undervoltage Detection Level
Name
Stall Prevention Selection during Acceleration
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
common_TMonly
Cold start
Hot start
Motor current (%)
150
200
E2-01 = 100% motor current
Setting Range
150 to 210 Vdc
Setting Range
0 or 1
Default
Determined by E1-01
Setting Range
0 to 2
Default
1
Default
1