E: Motor Parameters

E parameters cover V/f pattern and motor data settings.
◆ E1: V/f Pattern
E1-01: Input Voltage Setting
Adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.). Set this parameter to the
nominal voltage of the AC power supply.
NOTICE: Set parameter E1-01 to match the input voltage of the drive. The drive input voltage (not motor voltage) must be set in E1-01
for the protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.
No.
E1-01
<1>
<1> Values shown here are specific to 200 V class drives; double the values for 400 V class drives.
E1-01 Related Values
The input voltage setting determines the overvoltage and undervoltage detection levels.
Setting Value of
Voltage
200 V Class
All settings
setting ≥ 400 V
400 V Class
setting < 400 V
Note: The braking transistor operation levels are valid for the internal braking transistor of the drive. When using an external CDBR
braking chopper, refer to the instruction manual of that unit.
E1-03: V/f Pattern Selection
No.
E1-03
Note: Parameter is not reset to the default value when the drive is initialized using A1-03.
V/f Pattern Settings E1-04 to E1-13
Figure 5.13
illustrates the V/f pattern setting.
NOTICE: The motor may require more acceleration torque with drive operation than with a commercial power supply. Set a proper V/f
pattern by checking the load torque characteristics of the elevator to be used with the motor.
No.
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
<5>
E1-12
<5>
E1-13
<1> Setting range depends on the control mode being used. CLV allows a setting range of 10.0 to 120.0 Hz, while CLV/PM allows a setting range
of 4.0 to 120.0 Hz.
<2> Default setting is determined by the control mode (A1-02).
<3> Values shown here are for 200 V class drives. Double values when using a 400 V class unit.
<4> Default setting is determined by the drive model (o2-04).
<5> Parameter ignored when E1-11 and E1-12 are set to 0.0.
<6> Auto-Tuning will set E1-13 to the same value as E1-05.
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Parameter Name
Input Voltage Setting
E1-01
ov Detection Level
410 V
820 V
820 V
Parameter Name
V/f Pattern Selection
Parameter Name
Maximum Output Frequency
Maximum Voltage
Base Frequency
Middle Output Frequency
Middle Output Frequency Voltage
Minimum Output Frequency
Minimum Output Frequency Voltage
Middle Output Frequency 2
Middle Output Frequency Voltage 2
Base Voltage
5.5 E: Motor Parameters
Setting Range
155 to 255 V
(Approximate Values)
Braking Transistor Operation Level
394 V
788 V
788 V
Setting Range
F
Setting Range
10.0 to 120.0 Hz
0.0 to 255.0 V
<3>
0.0 to 120.0 Hz
0.0 to 120.0 Hz
0.0 to 255.0 V
<3>
0.0 to 120.0 Hz
0.0 to 255.0 V
<3>
0.0 to 120.0 Hz
0.0 to 255.0 V
<3>
0.0 to 255.0 V
<3>
Default
230 V
Uv Detection Level (L2-05)
190 V
380 V
350 V
Default
F
Default
<1>
<2>
<3>
<2>
<2>
<2> <3> <4>
<2>
<3> <4>
0.0 Hz
0.0 V
<3>
0.0 V
<3> <6>
169
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents