B.3 Parameter Table

◆ H: Multi-Function Terminals

H parameters assign functions to the multi-function input and output terminals.
H1: Multi-Function Digital Inputs
No.(Addr.)
Name
H1-03
Terminal S3 Function Selection
(400H)
H1-04
Terminal S4 Function Selection
(401H)
H1-05
Terminal S5 Function Selection
(402H)
H1-06
Terminal S6 Function Selection
(403H)
H1-07
Terminal S7 Function Selection
(404H)
H1-08
Terminal S8 Function Selection
(405H)
<19> With the speed reference priority d1-18 is set to 0 or 3, the default settings for parameters H1-03 to H1-07 governing input terminals S3 to S7
are: 24, 13, 3, 4, and 5 respectively. When d1-18 is set to 1 or 2, the default settings for H1-03 to H1-07 become 50, 54, 51, 53, and F
respectively.
H1-
Function
Setting
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog reference selection
7
Accel/decel Ramp Selection 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
F
Not Used (Through Mode)
14
Fault Reset
15
Fast Stop (N.O.)
16
Motor 2 Selection
17
Fast Stop (N.C.)
352
All Modes
Assigns a function to the multi-function digital inputs.
Refer to page
352
to page
353
for a description of setting values.
Note: Unused terminals should be set to F.
H1 Multi-Function Digital Input Settings
All Modes
When input terminals are set to Multi-Step Speed References 1 through 3, switching combinations of those
terminals will create a multi-step speed sequence using the speed references set in d1-01 through d1-08.
All Modes
Closed: Jog frequency reference (d1-17) selected.
The Jog frequency can be used when the speed reference selection is not assigned to input terminals (b1-01 ≠ 1)
and the speed reference priority is set to use the multi-step speed reference (d1-18 = 0 or 3).
All Modes
Used to switch between accel/decel ramp 1 (set in C1-01, C1-02) and accel/decel ramp 2 (set in C1-03, C1-04).
When combined with another input terminal set for "Accel/Decel ramp 2" (H1-
switch between accel/decel ramp 3 (set in C1-05, C1-06) and accel/decel ramp 4 (set in C1-07, C1-08).
All Modes
Closed: No drive output
All Modes
Open: No drive output
All Modes
Select this setting when using the terminal in a pass-through mode. The terminal does not trigger a drive function
but can be used as digital input for the controller the drive is connected to.
All Modes
Closed: Resets faults if the cause is cleared and the Up/Down command is removed.
All Modes
Closed: Decelerates to stop at the Fast Stop ramp set to C1-09.
All Modes
Open: Motor 1(E1-
, E3-
Closed: Motor 2 (E2-
, E4-
All Modes
Open: Decelerates to stop at the Fast Stop ramp set to C1-09.
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Description
Description
)
)
Setting
Page
Default:
<19>
Min: 3
Max: 79
Default:
<19>
Min: 3
Max: 79
Default:
<19>
common_
Min: 3
TMonly
Max: 79
Default:
<19>
Min: 3
Max: 79
Default:
<19>
Min: 3
Max: 79
Default: F
Min: 3
Max: 79
Page
common_
TMonly
common_
TMonly
common_
TMonly
= 1A), the drive can also
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
184
184
184
184
184
184
184
184
184
184
185
185
185
185
185
185
186
185