Control Circuit Wiring - YASKAWA L1000A Technical Manual

Ac drive for elevator applications; type: cimr-luxa; 200 v class: 3.7 to 110 kw (5 to 150 hp); 400 v class: 3.7 to 132 kw (5 to 200 hp) a
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

3.8

Control Circuit Wiring

◆ Control Circuit Connection Diagram
Refer to Standard Connection Diagram on page 52
◆ Control Circuit Terminal Block Functions
Drive parameters determine which functions apply to the multi-function digital inputs (S3 to S8), multi-function digital
outputs (M1 to M6), multi-function photocoupler outputs (P1-C1, P2-C2), multi-function analog inputs (A1, A2), and
multi-function analog monitor output (FM, AM). The default setting is listed next to each terminal in
53.
NOTICE: Equipment Hazard. Improper equipment sequencing could shorten useful life of the electrolytic capacitors and circuit relays
of the drive. Refrain from switching an input contactor more often than once every 30 minutes. Normally the drive I/O should be used to
stop and start the motor.
WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive
with untested control circuits could result in death or serious injury.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Failure to comply
may result in death or serious injury.
NOTICE: Frequently switching the drive power supply to stop and start the motor can damage the drive.
NOTICE: To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the drive power
supply off and on more than once every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the motor.
Note: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring
practices could result in drive malfunction due to loose terminal connections.
Input Terminals
Table 3.6
lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
input.
Type
No.
S1
Up Command (Closed: Up, Open: Stop)
Down Command (Closed: Down, Open: Stop)
S2
S3
Multi-function input 1 (Nominal Speed)
Multi-function input 2 (Inspection Operation)
S4
Digital Inputs
S5
Multi-function input 3 (Intermediate Speed 1)
Multi-function input 4 (Leveling Speed)
S6
S7
Multi-function input 5 (Not used)
Multi-function input 6 (Not used)
S8
SC
Multi-function input common
Digital Input
0 V
SN
Power Supply
+24 Vdc
SP
Safe Disable input 1
H1
Safe Disable
Safe Disable input 2
H2
Inputs
<1>
Safe Disable function common
HC
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
when wiring the drive control circuit terminals.
Table 3.6 Control Circuit Input Terminals
Terminal Name (Function)
Function (Signal Level) Default Setting
Photocoupler
24 Vdc, 8 mA
Use the wire link between terminals SC and SN or between SC and SP to select
sinking or sourcing, and to select the power supply.
24 Vdc, 150 mA (only when DI-A3 is not used)
Use the wire jumper between terminals SC and SN or between SC and SP to select
sinking or sourcing, and to select the power supply.
24 Vdc, 8 mA
One or both open: Drive output disabled
Both closed: Normal operation
Internal impedance: 3.3 kΩ
Off time of at least 1 ms
Set the S3 jumper to select sinking or sourcing, and to select the power supply.
Common for the Safe Disable function
3.8 Control Circuit Wiring
Figure 3.1
on page
Page
352
75
427
3
69

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents