Setting 1F: Not used (Through mode)
When set to 1F, an input does not affect any drive function, but the input level can still be read out by a PLC via a
communication option or MEMOBUS/Modbus communications.

◆ H4: Multi-Function Analog Outputs

These parameters assign functions to analog output terminals FM and AM for monitoring a specific aspect of drive
performance.
H4-01, H4-04: Terminal FM, AM Monitor Selection
Sets the desired drive monitor parameter U -
Monitor Parameters on page 247
be used for analog output.
Example: Enter "103" for U1-03.
No.
H4-01
H4-04
A setting of 031 or 000 applies no drive monitor to the analog output. With this setting, terminal functions as well as FM
and AM output levels can be set by a PLC via a communication option or MEMOBUS/Modbus (through mode).
H4-02, H4-03: Multi-Function Analog Output Terminal FM Gain and Bias
H4-05, H4-06: Terminal AM Gain and Bias
Parameters H4-02 and H4-05 set the terminal FM and AM output signal level equal to 100% of the monitor (gain).
Parameters H4-03 and H4-06 set the bias added to the monitor output for terminals FM and AM. Both are set as a
percentage, where 100% equals 10 Vdc analog output. The output voltage of both terminals is limited to 10 Vdc.
Select an output signal range between 0 to +10 Vdc or -10 to +10 Vdc using parameters H4-07 and H4-08.
illustrates how gain and bias settings work.
No.
H4-02
H4-03
H4-05
H4-06
Using Gain and Bias to Adjust Output Signal Level
When viewing a gain setting parameter (H4-02 or H4-05) on the digital operator, the analog output will supply a voltage
signal equal to 100% of the monitor value (including changes made from bias and gain settings). When viewing a bias
setting parameter (H4-03 or H4-06), the analog output voltage will supply a signal equal to 0% monitor value (including
changes made from bias and gain settings).
Example 1: Set H4-02 to 50% for an output signal of 5 V at terminal FM when the monitored value is at 100%.
Example 2: Set H4-02 to 150% for an output signal of 10 V at terminal FM when the monitored value is at 76.7%.
200
to output as an analog value via terminal FM and AM. Refer to
for a list of all monitors. The "Analog Output Level" column indicates if a monitor can
Name
Terminal FM Monitor Selection
Terminal AM Monitor Selection
Name
Terminal FM Gain
Terminal FM Bias
Terminal AM Gain
Terminal AM Bias
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Setting Range
000 to 999
000 to 999
Figure 5.31
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
U:
Default
102
103
Default
100.0%
0.0%
50.0%
0.0%