D.3 UL and CSA Standards

◆ UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing
and evaluation, and determined that their stringent standards for product safety have been met. For a product to receive
UL certification, all components inside that product must also receive UL certification.
Figure D.6
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. To ensure continued
compliance when using this drive in combination with other equipment, meet the following conditions:
Installation Area
Do not install the drive to an area greater than pollution severity degree 2 (UL standard).
Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of
closed-loop crimp terminals when wiring the drive main circuit terminals on models CIMR-L 2A0085 to 2A0415 and
4A0045 to 4A0260. Use only the tools recommended by the terminal manufacturer for crimping.
The wire gauges listed in
Table D.3
gauge selections.
Note: The mark
indicates the terminals for protective ground connection. (as defined in IEC60417-5019)
Grounding impedance;
200 V: 100 Ω or less
400 V: 10 Ω or less
Table D.3 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
Model
CIMR-L
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
2A0018
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
2A0025
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
2A0033
B1, B2
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Figure D.6 UL/cUL Mark
and
Table D.4
are Yaskawa recommendations. Refer to local codes for proper wire
Recommended Gauge
Terminal
AWG, kcmil
10
10
10
Applicable Gauge
AWG, kcmil
12 to 10
12 to 10
12 to 10
14 to 10
12 to 10
8
10 to 6
8
10 to 6
10 to 6
14 to 10
8
10 to 8
6
8 to 6
8
8 to 6
6
12 to 10
8
10 to 8
D.3 UL and CSA Standards
Screw
Tightening Torque
Size
N m (lb.in.)
1.2 to 1.5
M4
(10.6 to 13.3)
1.2 to 1.5
M4
(10.6 to 13.3)
2 to 2.5
M5
(17.7 to 22.1)
1.2 to 1.5
M4
(10.6 to 13.3)
2 to 2.5
M5
(17.7 to 22.1)