M320 Clearance Requirements

Copyright © 2015, Juniper Networks, Inc.

Figure 25: Airflow Baffle Template

Maintaining the M320 Air Filters on page 267
Maintaining the M320 Fan Trays on page 268
Troubleshooting the M320 Cooling System on page 287
When planning the installation site, you need to allow sufficient clearance around the
rack (see
Figure 26 on page
For the cooling system to function properly, the airflow around the chassis must be
unrestricted.
"M320 Cooling System Description" on page 21
router.
For service personnel to remove and install hardware components, there must be
adequate space at the front and back of the router. We recommend that you allow at
least 30 in. (72.6 cm) in front of the rack and 24 in. (61.0 cm) behind the rack.