Clearance Requirements for Hardware Maintenance of ACX7100-32C
Routers
When planning the site for installing an ACX7100-32C router, you must allow sufficient clearance
around the installed chassis (see
Figure 17: Clearance Requirements for Hardware Maintenance of ACX7100-32C Routers
• For the cooling system to function properly, the airflow around the chassis must be unrestricted. See
"Cooling System and Airflow in ACX7100-32C Routers" on page 17
airflow through the chassis.
• If you are mounting an ACX7100-32C router in a rack or cabinet that has other equipment installed,
ensure that the exhaust from other equipment does not blow into the intake vents of the chassis.
• Leave at least 6 in. (15.2 cm) clearance at the front and rear of the chassis for airflow and to
accommodate the interface and power cable bend radius.
• Leave adequate space at the front and rear of the router for service personnel to remove and install
hardware components. Allow at least 24 in. (61 cm) of space both at the front and the rear of the
router.
Figure 17 on page
38).
for more information about the
38