6.
Move jumper (J2J2) from the normal position covering pins 1-2 to the reset/clear position covering pins 2-3.
7.
Wait five seconds and remove power.
8.
Move the jumper (J2J2) back to the normal default position (pins 1-2).
9.
Re-install the processor air duct and the right-side riser card assembly.
10. Close the server chassis. See (RL) in Chapter 6 for instructions.
11. Power up the server.
The CMOS is now cleared and can be reset by going into the BIOS setup.
Removing power before performing the CMOS clear operation causes the system to automatically power up and
NOTE:
immediately power down after the procedure is followed and power is re-applied. If this happens, remove the power cord again,
wait 30 seconds, and reconnect the power cord. Then, power up the system and proceed to the <F2> BIOS Setup utility to reset
the settings.