How to Use the Control Keys

+RZWR8VHWKH&RQWURO.H\V
AFC-600 Operations PN 51033:A 3/8/99
Technical Manuals Online! - http://www.tech-man.com
The control panel provides five Control Keys: A
A
A
, S
LARM
CTIVATE
YSTEM
/
Use the
ACKNOWLEDGE
STEP
trouble signals. When you press the
following:
Silences the panel sounder
Changes all active LED indicators from flashing to steady
Sends an Acknowledge message to the History buffer and installed printers, CRT-2
terminals, and terminal mode LCD-80s
Sends a signal to silence the sounders on the LCD-80 and ACS annunciators
You can also press the
ACKNOWLEDGE
more than one alarm or trouble exists, the control panel displays the next alarm or
trouble for 3 seconds (or until you press the
next alarm or trouble.
Use the
ALARM SILENCE
ALARM SILENCE
all audio and visual devices connected to Notification Appliance Circuits. When you
press the
key, the control panel does the following:
ALARM SILENCE
Turns off the panel sounder
Turns off all silenceable output circuits
Lights the
ALARM SILENCED
Sends an Alarm Silenced message to the History buffer and installed printers,
CRT-2 terminals, and terminal mode LCD-80s
Use the
ALARM ACTIVATE
ALARM ACTIVATE
outputs or to test notification appliances. To prevent accidental activation, you must
press the
ALARM ACTIVATE
key, the control panel does the following:
Turns on all silenceable NACs
Turns off the
ALARM SILENCED
Sends a Manual Evacuate message to the History buffer and installed CRT-2
terminals, printers, and terminal mode LCD-80s
6<67(0 5(6(7
Use the
SYSTEM RESET
key, the control panel does the following:
SYSTEM RESET
Turns off all alarm-activated control/relay modules, NAC circuits, and Panel Circuits
Breaks resettable power to four-wire detectors
Sends an "All Systems Normal" message to the History buffer, and installed CRT-2
terminals, and terminal mode LCD-80s
If any alarm or trouble exists after you press the
outputs, and panel audio and visual indicators will reactivate.
$03
(67
Use the
/
7
LAMP TEST
When you press and hold the
Lights all control panel LEDs
Turns on the panel sounder
Lights all segments of the LCD display
CKNOWLEDGE
R
, and L
T
.
ESET
AMP
EST
key to respond to new alarm or
/
ACKNOWLEDGE
STEP
/
ACKNOWLEDGE
STEP
key to display multiple alarms or troubles. If
/
STEP
ACKNOWLEDGE
key to silence the panel sounder and turn off
LED
key to manually activate all programmed
key for 2 seconds. When you press the
LED
key to reset the control panel. When you press the
SYSTEM RESET
key to test the control panel LEDs and panel sounder.
key, the control panel does the following:
LAMP TEST
 +RZ WR 8VH WKH &RQWUROV
/S
,
TEP
ALARM SILENCE
key, the control panel does the
key), then displays the
/
STEP
ALARM ACTIVATE
key, NACs, control
,
13