www.PDF-Zoo.com
When applying power to this control unit, apply primary (AC) first, followed by batteries, as
described in "Power-Up Procedure" in Section 2.11.
Alarm, Trouble and Supervisory LEDs will flash on and off until the event(s) has been acknowl-
edged (TONE or ALARM SILENCE), at which point the LED will illuminate steadily.
$&3RZHU
Green LED that illuminates steadily to indicate
presence of AC power.
6\VWHP$ODUP
Red LED that flashes when an alarm occurs.
5HOHDVH
Red LED that illuminates steadily when release
occurs. After the Discharge Timer has expired, the
LED will flash.
6XSHUYLVRU\
Yellow LED that flashes upon activation of a
supervisory device (such as tamper switch) on
Zone 4.
6\VWHP7URXEOH
Yellow LED that flashes for any trouble condition,
including those associated with optional boards.
&LUFXLW7URXEOH
Yellow LED that flashes for trouble conditions on output circuits (notification and releasing
circuits).
$ODUP6LOHQFHG
Yellow LED that illuminates steadily when the ALARM SILENCE switch has been pushed after an
alarm.
3RZHU7URXEOH
Yellow LED that flashes for low or disconnected batteries and earth fault conditions.
%DWW
Yellow LED that illuminates steadily on motherboard when battery is low or not detected.
(DUWK
Yellow LED that illuminates steadily on motherboard during a ground fault condition.
0LFUR)DLO
Yellow LED that illuminates on motherboard when watchdog timer detects microprocessor failure.

System Operation

BATT EARTH
MICRO
FAIL