Service Menu Test; Ervice Enu Est Out - Notifier AFP-2800 Operator's Manual

Fire alarm panel
Hide thumbs Also See for AFP-2800:
Table of Contents

Advertisement

Page 52
4.3.7.2
4.3.7.2
4.3.7.2
4.3.7.2
S S S S
ERVICE
ERVICE
ERVICE
ERVICE
In this screen a Digital Output may be tested to verify it's ability to operate when required.
DIGITAL OUTPUT TEST MENU
01 OCT 1999 14:44:37
TESTING DIGITAL OUTPUT POINT
POINT STATUS:
SCRIPT PROCESSING PAUSED
TEST BUTTON WILL TOGGLE STATE
ISOL
All Script processing is paused while in test mode to provide positive control of the output state. Script
automatically recommence processing when test mode is exited.
Test mode will automatically exit after 10 minutes from the last button press to prevent the system remaining
off line.
If a digital output does not have a control script and is set on during test mode, the output will remain on
permanently until turned off through test mode. This can be a useful function for testing purposes during
commissioning.
Note:
As the Dout tests activate the output at the remote module, the module itself is tested as well as the panel to module
communications.
4.3.7.3
4.3.7.3
4.3.7.3
4.3.7.3
S S S S
ERVICE
ERVICE
ERVICE
ERVICE
This function will run a load test on the batteries for 15 seconds, and if a battery fault is detected, it will be
displayed and logged as such to the history. A successful Battery Test will clear a battery fault. The panel also
performs a short battery integrity test every hour.
Note: The battery test will not run if there is a Mains Fail condition, so as not to further deplete the battery charge.
© N
I
P
OTIFIER
NERTIA
TY
www.PDF-Zoo.com
M M M M
– T
– T
– T
– T
ENU
ENU
ENU
ENU
EST
EST
EST
EST
A = 0
F = 0
I = 0
N = 1
1.2.O3
OFF
TEST
BACK
M M M M
– T
– T
– T
– T
ENU
ENU
EST
EST
ENU
ENU
EST
EST
L
, 2001
TD
firealarmresources.com
AFP-2800 - Fire Indicator Panel – Panel Operation
- D
- D
- D
- D
OUT
OUT
OUT
OUT
Action:
An ISOL button is provided so that the point can
be easily isolated during the test period, this button
will toggle to DEISOL if the point is already
isolated.
A single press of the TEST button will toggle the
output between On and Off.
Pressing the BACK button will return to the
previous screen.