Advertisement

1010/2020 O
M
PERATORS
ANUAL
A
S
LTER
TATUS MENU
The ALTER STATUS menu provides the following options:
Selection
Abbreviation
1
ISO
2
CTL
3
DSEN
4
TIME
5
DIA
6
WALK
W
T
P
ALK
EST
ROCEDURE
Walk test is a feature used for 1 man detector testing.
Menu options are as follows:
Selection
Abbreviation
1
SEL
2
UNP
3
UNI
4
TEST
5
UNTST
6
EXIT
The procedure for walk test is as follows.
Enter walk test mode
Select one or more loops for walk testing
Test detectors & input modules.
Print reports
Exit walk test mode returning panel to normal.
Description
I
F
SOLATE
UNCTION
Provided the ability to isolate / de-isolate individual points on the system.
Enter the detector, module or zone number and then select Y to isolate
or N to de-isolate. Press backspace to exit.
C
M
ONTROL
This provides the ability to manually activate / de-activate any control
point (CMX output) on the System. Enter the LxxMxx then select Y/N
D
S
ETECTOR
Provides the ability to change each detectors sensitivity level. Sensitivity
can be set to L=Low, M=Medium, H=High.
T
C
IME
HANGE
Provides the ability to change the system clock time.
S
D
YSTEM
IAGNOSTICS
Invokes a self diagnostic systems check.
W
T
:
ALK
EST
Invokes walk test mode for 1 man detector testing. Walk test will
automatically exit after 15 minutes of no alarms. Please refer to walk test
heading below for further information.
:
Description
Select Loops for Walk Test:
Select the loops to perform walk test on.
Unprogrammed Device Report
Print a report to the printer showing a list of all unprogrammed devices
on the loop (s).
Uninstalled Devices
Print a report to the printer showing a list of all uninstalled devices on the
loop (s).
Tested Device Report
Print a report to the printer showing a list of all tested devices on the
loop (s).
Untested Device Report
Print a report to the printer showing a list of all untested devices on the
loop (s).
Exit Walk Test Mode:
It is important that walk test be correctly exited to return the system back
to it's normal condition. (The panel will automatically exit walk test mode
after 15 minutes of no alarms.)