6.6

Operation frequency

6.6.1
 : Starting frequency
 Function
[Parameter setting]

6
6.6.2
 : Operation starting frequency
 : Operation starting frequency hysteresis
 Function
[Parameter setting]


Starting frequency
The frequency set with  is put out as soon as operation is started.
Use the  parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
Title
Function
Starting frequency
Output frequency (Hz)
Starting frequency 
Operation signal (F-CC)
Run/stop control with frequency setting signals
The Run/stop of operation can be controlled simply with frequency setting signals.
Title
Function
Operation starting frequency
Operation starting frequency hysteresis
Output frequency [Hz]

 +


 -

0.1-10.0 (Hz)
0
0.0- (Hz)
0.0- (Hz)
0
A
B
100% Frequency command value
F-18
Adjustment range
Default setting
Time
ON
OFF
Adjustment range
Default setting
When the frequency command signal
reaches the B point, the inverter
operates.
When decelerating, operation stops
when the frequency setting signal is less
than point A.
E6581595