Fskadp (Ocomc - Motorola MOSCAD 68P02958C00-B User Manual

Toolbox version 5.50
Table of Contents

Advertisement

## 1440
plug-in modem statistical information
Number of spikes received at last reception
Total number of spikes received
Number of illegal received frames
Piggyback hardware statistics
LEVEL : 40 - Execute statistics and zero counters.
LEVEL : 41 - Execute statistics but do not zero counters.
1. The number of spikes received the last time reception was operated.
2. The total number of spikes received.
3. From piggyback version 1.2 and on, the size of the maximum transmission buffer of piggyback (up to
32 bits).
FSKADP : Channel Access to INTRAC FSK Piggyback. (The transmission of lateral
MDLC INTRAC frames to radio / line). The module is executed as a
result of transmission from OCOMM module and is found under UART.
Diagnostic operation : Operated by DEVICE NAME : OCOMM
LEVEL : 0 , 1 , 2 , 3 , 4 , 10 , 11

FSKADP (OCOMC)

## 1500
LEVEL = 0
Line Configuration parameters :
Override Time on busy line-channel mS
Quiet Time on free line-channel mS
Wait for Channel-Access Timeout Sec
Line-channel warmup Time mS
Transmission Timeout Sec
Wait for Holdup Timeout Sec
Line-channel Holdup Time mS
Line-channel Shutup Time mS
Current status of line :
Line-channel quiet time mS
Line-channel busy time mS
Line channel access parameters:
1. During transmission, if "Channel busy" is detected, this parameter will determine the waiting time
(in msec) before forcing transmission onto a channel (even if the channel is still busy). Setting this
parameter to "0", will terminate the option.
2. Quiet channel period (in msec) before transmission. Setting this parameter to "0", will terminate the
waiting time and transmission will start immediately after the "free channel" detection.
3. Maximum waiting time (in msec) for available channel for transmission. If at the end of this period,
the channel is not available, the system provides a failure notice and the transmission attempts will
be terminated.
4. Transmits a constant tone during this period (in msec), before data transmission starts.
(till 225)
C-73
Software Diagnostics Output
: %% 1
: %% 2
: %% 3
: %% 1
: %% 2
: %% 3
: %% 4
: %% 5
: %% 6
: %% 7
: %% 8
: %% 9
: %% 10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Moscad

Table of Contents