Error #1260: Tmrevent: Events/Timers Buffer is Full.
No more buffers for DI events and their related timers. Number of buffers can
be increased in expert screen in configuration.
Error #1261: Tmrevent: Events/Timers were Ignored – NO 'Get Event' for %% msec
DI events and/or related timers were not checked (by GtEvnt function in rungs)
during a time interval longer than the maximum time that was defined in the
expert screens, and therefore were ignored.
Error #1450: Ladder or C application needs I/O modules with DI, but Configuration I/O
modules do not have the expected amount of DI
Define more DI modules in Site Configuration.
Error #1500: 'TxIntrc' was called with invalid address 'ITxStn' %%
This error occurs when you call the TxIntrc function with the wrong StnAck
variable. See Intrac Protocols chapter in Advanced Features in the Application
Programmer manual.
Possible range: 0-2047.
Error #1501: 'TxIntrc' was called with invalid group 'ITxGrp' %%
This error occurs when you call the TxIntrc function with the wrong ITxGrp
variable. See Intrac Protocols chapter in Advanced Features in the Application
Programmer manual.
Possible range: 0-7.
Error #1502: 'TxIntrc' was called with invalid direction 'ITxDir' %%
This error occurs when you call the TxIntrc function with the wrong ITxDir
variable. See Intrac Protocols chapter in Advanced Features in the Application
Programmer manual).
Possible range: 0-1.
Error #1503: 'TxIntrc' was called with invalid value 'ITxDat' %%
This error occurs when you call the TxIntrc function with the wrong ITxDat
variable. See Intrac Protocols chapter in Advanced Features in the Application
Programmer manual.
Possible ranges:
Analog
from -512 to 511.
Counter
0-999
Bits
0-255
C-168