Error #1751: Invalid block
Invalid "C" block loaded to the RTU. Its calculated CRC does not match that of
the loaded block. Reload the "C" block.
Error #1752: User Application Error:
Occurs as a result of MOSCAD_error function usage in one of the "C" blocks
loaded to the RTU.
Error #1763: 'C' Block version is higher than system 'C' application version.
Consult product group.
Error #1764: 'C' block no. %% contain invalid name %% in the user_jumptable.
Check the function names entered in the user_jumptable. An invalid name is
one whose length is more than six characters or one which contains a blank or
other invisible character.
Error #1770: The Downloadable "C" function is running too long. Could not delete it from
table.
Occurs as a result of error in one of the "C" blocks loaded to the RTU.
Error #1790: Socket Opening failed.
Communication problem with MDLC over IP.
Error #1791: Socket Connection failed.
Communication problem with MDLC over IP.
Error #1810: Could not abort the master sessions. The master channels are not stopped.
Problem with C master session during Download.
Error #1900: Cannot push into queue - it has reached maximal size
Error in MDLC over IP. Buffers for transmission are coming into queue faster
than port can take them. Up to 255 messages may be stored in transmission
queue prior to transmission from SLIP line. This error occurs if trying to
transmit more than this.
Error #1904: Destination site ID %% not supported
Error in MDLC over IP. Site ID does not appear in the IP Conversion Table.
Check if Site has IP address or if Site ID is correct.
Error #1905: Sync transmission is not supported
Error in MDLC over IP. RTU cannot send Sync frames through this link. Error
is obsolete.