Error #111:
From Site : %%Link : %% can not communicate with current unit
Communication was initiated by a site which is not defined in the Site table.
Error #112:
Trouble in queue: %%
Illegal management of linked buffers.
Error #113:
Illegal control byte : %%
Memory overwrite in a buffer that passed a CRC check. The buffer is dumped
into the heap.
Error #114:
Illegal buffer : %%
The Transport Multiplex layer can not understand a buffer that passed a CRC
check. This buffer is dumped into the heap.
Error #115:
Application Id not exists : %%
Applying to an application that does not exist in the RTU. This may occur when
using a new version of Tool Box with new features to communicate with an
older RTU that is not familiar with those new features.
Error #116:
Machine code illegal : %%
Due to a bug in the Transport Multiplex layer, the 'states machine' has reached
an illegal state.
Error #117:
Can't talk with master because unit was not defined as Slave !! OR flag Master
is Set but Unit was not defined as Master !!
For system software developers only. Consult product group.
Error #120:
Can not get characters from existing buffer
May indicate system software error. Consult product group.
Error #121:
Illegal compilation of SEND output
Indicates a software error in the Application Programmer. Consult product
group.
Error #140:
Invalid Link ID, network layer: %%, Dest Site: %%,
Dest Link: %%, Dest Port: %%
The network layer in a RTU is asked to transfer a communication buffer to the
Dest Site, Dest Link & Dest port but the specific link is not known to this RTU
(since other links are defined).
C-136
Error Messages