Mdlc Network Layer - Motorola MOSCAD 68P02958C00-B User Manual

Toolbox version 5.50
Table of Contents

Advertisement

Send broadcast reset after restart <YES/NO>
Specify YES to broadcast to all units defined after Reset Load in order to synchronize at
Transport Multiplex level.
Restart declaration time out <5-200> Sec
Time interval between two Restart control frames at Transport Multiplex level.
Time out for URGE transmission after hole detection <0-3000> Sec.
The period of time after which an "urge" frame will be issued if a gap formed at Transport
Multiplex level. A response to the urge frame means that the gap will never be filled since all
Data Link layer retries have already been exhausted.
Size of TX queue <30-200>
Since Transport Multiplex consumes buffers for transmission, the number of buffers is limited
via this parameter in order to prevent HP-Tx from being emptied completely.
No. of retries for 'URGE frame' <0-9>
The number of times an urge frame will be retransmitted.
Terminal emulation (application) support
Support for terminal emulation within the application. The valid values are Yes/No.
Health-check (application) support
Support for health check within the application. The valid values are Yes/No.

MDLC Network Layer

Network Layer
System configuration stock size <1-50>
Number of paths the Network layer is allowed to learn. This parameter is for future use. In
the current version, Network can learn only one path even if a different value is specified.
General Communication
Addr. range response for 'All RTU simulation' <Site ID +- Range> [0]:
Assigning alternate addresses to an RTU. If the basic address is X and the range is Y, then the
unit responds to all calls in the range of {X,X+1,...,X+Y}. If the range is -Y, the unit responds
to all calls in the range of {X-Y, X-Y+1, ..., X}.
This parameter is for field simulation in laboratory conditions and for the Dual CPU
mechanism.
5-46
Site Configuration
[YES]:
[30]:
[15]:
[160]:
[0]:
[Yes]:
[Yes]:
[1]: