Motorola MOSCAD 68P02958C00-B User Manual page 463

Toolbox version 5.50
Table of Contents

Advertisement

Error #1602: Failed testing INTRAC modem piggyback (CTS signal)
Hardware problem in modem.
Error #1638: INTRAC system table: invalid radio warmup time (R_Ptt) %%
Invalid R_Ptt value in the INTRAC system tables (database builder).
Possible range: 10-60000 msec.
Error #1639: INTRAC system table: invalid radio override time (ROvrid) %%
Invalid ROvrid value in the INTRAC system tables (database builder).
Possible range: 10-60000 msec.
Error #1640: INTRAC system table: invalid radio quiet time (RQuiet) %%
Invalid RQuiet value in the INTRAC system tables (database builder).
Possible range: 0-60000 msec.
Error #1641: INTRAC system table: invalid line warmup time (L_Ptt) %%
Invalid L_Ptt value in the INTRAC system tables (database builder).
Possible range: 10-60000 msec.
Error #1642: INTRAC system table: invalid line override time (LOvrid) %%
Invalid LOvrid value in the INTRAC system tables (database builder).
Possible range: 10-60000 msec.
Error #1643: INTRAC system table: invalid line quiet time (LQuiet) %%
Invalid LQuiet value in the INTRAC system tables (database builder).
Possible range: 0-60000 msec.
Error #1700: Failed initiating GPS port
Port 2, connected to GPS, cannot be initialized, because of hardware problem.
Error #1701: Transmission failure to GPS
Transmission to GPS failed because of hardware problem.
Error #1750: Insufficient dynamic memory. Needed: %%
Cannot allocate memory for "C" block because the size indicated in Site
Configuration is insufficient.
C-171
Error Messages

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Moscad

Table of Contents