Motorola MOSCAD 68P02958C00-B User Manual page 85

Toolbox version 5.50
Table of Contents

Advertisement

Link Layer Parameters for TCP/IP Port 1
The following parameters relate to the MDLC Over IP technology. The range of possible is
specified in < > symbols. The default is specified in square brackets (for example: [80]). You
can change this default.
Link name <LINE 1-LINE 29>
All RTUs and IP Gateways use the same line.
IP port number <1-65535>
This number is common to all RTUs and IP Gateways connected to the link. This number
identifies the MDLC.
It is important that this number not be in use as specified by the TCP/IP standard RFC0960.
Maximum rows in conversion table <0-255>
Maximum number of sites with which the RTU can communicate.
TX to failed RTU every <> min <0-30>
0 is DISABLE.
Periodic check of failed RTU
This option cannot be enabled in MDLC Over IP. Not applicable for IP Gateway.
TCP/IP Allocations/Settings
To tune the advanced TCP/IP and Gateway parameters, one must be familiar with the TCP/IP
drivers, and the internal mechanism of the Gateway. Therefore, it is recommended not to
change these parameters unless it is necessary, and you are aware of the consequences. If you
enter an incorrect range, Toolbox displays a dialog box with the valid parameter range.
Clock service interval (MS) <30-100>
Time in ms between clock service.
Boot Delay (Sec) <0-255>
Boot time
Max Sockets <0-100>
Maximum number of sockets
Max UDP TX Packets <2-20>
Maximum number of packets on UDP sending queue
Max UDP RX Packets <2-20>
Maximum number of packets on UDP receive queue
Max TCP TX Packets <2-30>
Maximum number of packets on TCP sending queue
Max TCP RX Packets
Possible values: 2048, 4096
Maximum number of packets on TCP receive queue
5-28
Site Configuration
[LINE 1]
[2002]
[255]
[0]
[Disable]
[30]
[255]
[50]
[4]
[4]
[10]
[2048]