Communication Buffer Size <500-8192>
Allows the definition of the maximum size of the communication buffers (in bytes).
If you entered an incorrect range, Toolbox displays a dialog box with the valid parameter
range. Click OK to dismiss the dialog box and enter the correct value.
Task Allocation
Overall Tasks <1-20>
Allows the definition of overall concurrent application tasks.
Dedicated CMD Tasks <0-10>
Allows the definition of concurrent Command tasks (dedicated for sending commands).
Dedicated DATA Tasks <0-15>
Allows the definition of concurrent Data tasks (dedicated for polling RTUs and for
downloading parameters).
Dedicated SERVICE Tasks <0-5>
Allows the definition of concurrent Service tasks (dedicated for sending/reading RTUs time).
If you entered an incorrect range, the Toolbox displays a dialog box with the valid parameter
range. Click OK to dismiss the dialog box and enter the correct value.
Request Allocation
Overall Pending Requests <1-125>
Allows the definition of overall pending requests, (must equal the combined sum of Pending
CMD, Data and Service Requests).
Pending CMD Requests<0-105>
Allows the definition of minimum pending command requests from the SCADA).
Pending DATA Requests<0-105>
Allows the definition of minimum pending data requests from the SCADA).
Pending SERVICE Requests<0-105>
Allows the definition of minimum pending service requests from the SCADA).
5-57
Site Configuration
[8192]
[6]
[1]
[1]
[1]
[30]
[10]
[10]
[10]