Enclos-
ures
7
6
5
4
18.7
3
14.8
2
10.8
1
6.8

UPS Selection

This section provides information that can be used when selecting a UPS for use with the EVA. The
four HP UPS products listed in
comparison.
Table 50
and with various UPS ERM (Extended Runtime Module) options.
The load imposed on the UPS for different disk enclosure configurations are listed in
52, and
Table
NOTE:
The specified power requirements reflect fully loaded enclosures (14 disks) .
Table 49 HP UPS models and capacities
UPS Model
R1500
R3000
R5500
R12000
Table 50 UPS operating time limits
Load (percent)
R1500
100
80
50
EVA4x00
1875
1837
6269
1475
1446
4933
1075
1054
3596
676
662
2259
Table 49
identifies the amount of time each UPS can sustain power under varying loads
53.
Capacity (in watts)
1340
2700
4500
12000
With standby battery
5
6
13
HP StorageWorks 4x00/6x00/8x00 Enterprise Virtual Array user guide
EVA6x00
31.5
3145
3082
10518
27.5
2746
2691
9181
23.5
2346
2299
7845
19.5
1946
1907
6508
15.5
1546
1516
5171
11.5
1147
1124
3835
7.5
747
732
2498
are available for use with the EVA and are included in this
Minutes of operation
With 1 ERM
23
32
57
EVA8x00
Table
51,
Table
With 2 ERMs
49
63
161
177