The following sections define the power supply condition reports.
0.3.en.01 NONCRITICAL condition—Blower speed
A
blower
is operating at a speed outside of the EMU specified range, possibly because of a bearing
problem. This can affect enclosure cooling and cause an element to fail. This condition report remains
active until the problem is corrected.
This error does not normally require immediate correction. However, an error of this type could
contribute to an element overheating.
HP recommends replacing the
To correct this problem, record all six characters of the condition report, then contact your HP authorized
service representative.
0.3.en.02 CRITICAL condition—Blower speed
A
blower
is operating at a speed that is significantly outside the EMU specified range, possibly
because of a bearing problem. This can cause the loss of cooling and cause an element to fail. The
error remains active until the problem is corrected.
HP recommends replacing the
To correct this problem, record all six characters of the condition report, then contact your authorized
service representative.
0.3.en.03 UNRECOVERABLE condition—Blower failure
A
blower
has stopped. The operational blower now operates at high speed and is a single point of
failure. This condition report remains active until the problem is corrected.
To correct this problem, record all six characters of the condition report, then contact your authorized
service representative.
0.3.en.04 UNRECOVERABLE condition—Blower internal
A power supply reported an internal
element to fail. HP recommends correcting the problem before the blower fails. This condition report
remains active until the problem is corrected.
To correct this problem, record all six characters of the condition report, then contact your HP authorized
service representative.
0.3.en.05 NONCRITICAL condition—Blower missing
A
blower
has been removed or is improperly installed. Even though the blower flaps close to maintain
the proper air flow, the reduced cooling capability can cause overheating, causing an element to
fail. This condition report remains active until the problem is corrected.
To correct this problem, record all six characters of the condition report, then contact your HP authorized
service representative.
blower
as soon as possible.
blower
as soon as possible.
blower
HP StorageWorks 4x00/6x00/8x00 Enterprise Virtual Array user guide
error that could affect enclosure cooling and cause an
151