APPENDIX 1. DETAILS OF THE ID SETTING SWITCH
The ID setting switch sets ID which specifies the slave by the EtherCAT master.
The ID can be chosen a proper value by the user.
The setting must be designated a 3-digit hexadecimal number between 000H and FFFH (decimal: between 0 and
4095). Designate 000H (0) if automatic allocation function is used.
Set the ID setting switch on the panel side when using the Hot Connect function.
For details of the Hot Connect function, refer to master system manual.
There are three methods for reading out the set ID. The master can be read out either of method.
(1) Reading the value in SII via Configuration Station Alias (Station Alias ID)
In the case of the ID setting switch on the panel is set to "0",
A saved value in 0004h of SII (Configuration Station Alias) is stored in ESC register 0012h (Configuration Station
Alias) when the power is supplied to NCW-3DNEC. The master should read this value.
●Initial value
The factory setting is "0" to 0004h of SII (Configuration Station Alias).
(2) Reading the ID setting switch via Configuration Station Alias (Station Alias ID)
In the case of the ID setting switch on the panel is set to a value except "0",
The value of the ID setting switch is stored in ESC register 0012h (Configuration Station Alias) when the power is
supplied to NCW-3DNEC. The master should read this value.
(3) Reading the ID setting switch via AL Status Code (Explicit Device ID)
In the case of the ID setting switch on the panel is set to a value except "0",
The value of the ID setting switch is stored in ESC register 0134h (AL Status Code) when the power is supplied to
NCW-3DNEC. The master should read this value.
65