iC7-Automation Air-cooled Enclosed Drives
Operating Guide
Model code
Frame
iC7-60EA3A05-1260
2 x AE11 +
2 x IE11
iC7-60EA3A05-1450
iC7-60EA3A05-1710
Cable lugs installed on both sides of the fixing hole
1
With copper cables, use copper lugs. With aluminum cables, use bimetallic lugs.
2
Use bimetallic lugs. No direct aluminum contact to the mains terminals.
3
10.5.3 Motor Cable Size Recommendation, 380–500 V
Table 34: Motor Cable Size Recommendation, 380–500 V
Model code
Frame
iC7-60EA3N05-206A
FE9
iC7-60EA3N05-245A
iC7-60EA3N05-302A
iC7-60EA3N05-385A
iC7-60EA3N05-480A
FE10
iC7-60EA3N05-588A
iC7-60EA3A05-385A
AE10 + IE10
iC7-60EA3A05-480A
Danfoss A/S © 2023.09
2
I
[A]
Cable [mm
]
N
1148
Cu 6 x (3x95+50)
Al 6 x (3x120+41 Cu)
1293
Cu 6 x (3x120+70)
Al 6 x (3x150+70 Cu)
1453
Cu 6 x (3x150+70)
Al 6 x (3x185+57 Cu)
2
I
[A]
Cable [mm
]
N
206
Cu 2 x (3x95+50)
Al 2 x (3x95+29 Cu)
245
Cu 2 x (3x95+50)
Al 2 x (3x95+29 Cu)
302
Cu 2 x (3x95+50)
Al 2 x (3x95+29 Cu)
385
Cu 2 x (3x95+50)
Al 2 x (3x95+29 Cu)
480
Cu 2 x (3x150+70)
Al 3 x (3x120+41 Cu)
588
Cu 2 x (3x150+70)
Al 3 x (3x120+41 Cu)
394
Cu 1 x (3x185+95)
Al 2 x (3x120+41 Cu)
490
Cu 2 x (3x120+70)
Al 2 x (3x150+70 Cu)
Maximum
Maxi-
Hole
cable size
mum
size of
2
[mm
]
number
the
of
mains
mains
termi-
cables
nal
(1)
[mm]
240 Cu/Al
8
Ø10.5
240 Cu/Al
8
Ø10.5
240 Cu/Al
8
Ø10.5
Maximum
Maxi-
Bolt
cable size
mum
size
2
[mm
]
num-
(1)
ber of
motor
cables
95 Cu/Al
2
M10
95 Cu/Al
2
M10
95 Cu/Al
2
M10
95 Cu/Al
2
M10
150 Cu/120
3
M10
Al
150 Cu/120
3
M10
Al
240 Cu/Al
4
M10
240 Cu/Al
4
M10
AQ330347384398en-000201 / 139Z8096 | 97
Specifications
Number
Hole size
of
of the
ground-
ground-
ing holes
ing termi-
on PE
nal [mm]
busbar
8
Ø10.5
8
Ø10.5
8
Ø10.5
Number of
Hole size
grounding
of the
holes on
grounding
PE busbar
terminal
[mm]
2
Ø10.5
2
Ø10.5
2
Ø10.5
2
Ø10.5
4
Ø10.5
4
Ø10.5
4
Ø10.5
4
Ø10.5