4 Receiving the Drive

4.1 Checking the Shipment

Procedure
1.
Examine the packaging and the drive for transport damage.
a.
-
If the drive was damaged during transport, contact the cargo insurance company or the carrier.
2.
Make sure that the items supplied and the information on the product label correspond to the order confirmation.
a.
-
If the shipment does not match the order, contact the vendor immediately.

4.2 Storing the Enclosed Drive

If it is necessary to store the product before installing it, follow these instructions.
Keep the product in the original packaging. Make sure that the ambient storage conditions correspond to these requirements:
Temperature: -40...+70 °C (-40...+158 °F)
Humidity: 0...95%, no condensation
Procedure for storage of 2–12 months
1.
If the package is kept in storage for more than 2 months, keep it in controlled conditions.
-
a.
Make sure that the temperature variation is small.
-
b.
Make sure that the humidity is less than 50%.
Procedure for storage of over 12 months (FE9 and FE10)
1.
If the package is kept in storage for more than 12 months, do these steps every 12 months, to reform the capacitors to
prevent damage to the capacitors.
-
a.
Connect power to the drive.
b.
-
Keep the power on for a minimum of 2 hours.
-
c.
Disconnect the power.
d.
-
Wait for the correct discharge time before removing the drive and storing it again.
Procedure for storage of several years
1.
If the package is kept in storage for several years, reform the capacitors every 12 months to prevent damage to the capaci-
tors.
a.
-
Connect a DC supply with adjustable current limit to the DC+ and DC- terminals.
-
b.
Set the current limit (250 mA). In case of parallel power units, multiply the value with the number of power units.
c.
-
Set DC voltage (1.35 * U
-
d.
Keep the power on for a minimum of 1 hour.
e.
-
Disconnect the DC supply from the DC+ and DC- terminals.
Danfoss A/S © 2023.09
AC), where U
is the drive nominal voltage.
n
n
Receiving the Drive
AQ330347384398en-000201 / 139Z8096 | 21