10.5 Cable Sizes
10.5.1 General Cable Size Information
The IEC cable sizing is based on the ambient temperature of 40 °C, cables laid side by side on cable ladders, maximum 9 cables per
ladder, and 3 ladders on top of each other. Use cable insulation that can withstand a temperature of at least 90 °C. Cables are XLPE
insulated, maximum conductor temperature 90 °C. In other conditions, refer to the local safety regulations, the input voltage, and
the load current of the drive.
The UL cable sizing is based on the ambient temperature of 40 °C (104 °F), 75 °C (167 °F) or 90 °C (194 °F) rated copper cables, and
multicore cables installed raceways or not stacked or bundled longer than 600 mm (24 in) without maintaining spacing. In other
conditions, refer to the local safety regulations, the input voltage, and the load current of the drive.
Use symmetrical cabling with system modules connected in parallel. Each module must have the same number of cables with an
equal cross-section.
The cable size tables for the air-cooled enclosed drives can be found with these links.
•
10.5.2 Mains Cable Size Recommendation, 380–500 V
•
10.5.3 Motor Cable Size Recommendation, 380–500 V
•
10.5.4 Mains Cable Size Recommendation, UL 480 V
•
10.5.5 Motor Cable Size Recommendation, UL 480 V
Danfoss A/S © 2023.09
A
B
11
-SFG
12
2
-XDF 5
21
11
REMOVE SADDLE JUMPERS:
XDJ: 3-5
12
22
XDJ: 4-6
3
4
6
42
43
44
45
45
RD
RD
RD
WH
WH
42
43
44
45
45
46
INPUT A+
INPUT B+
FB+
GND
GND
INPUT A-
X33
STO Connector
Micro SD Memory
-X4
card slot
RTC Battery
-X10
Type: BR1632
N O T I C E
21
22
6
4
3
46
47
48
-XD2.3 101
WH
WH
RD
RD
47
48
101
102
INPUT B-
FB-
24VDC IN
GND
X1
Fieldbus
Fieldbus
Ethernet
Ethernet
RJ 45
RJ 45
-X3.1
SERVICE ETHERNET
ON DOOR
102
61
62
63
64
WH
RD
WH
RD
WH
61
62
63
64
24VDC EXT.
GND
24VDC OUT
GND
X62
24VDC Supply
X2
X3
Fieldbus
X9
Ethernet
ICP
RJ 45
IX connector
-PGA
-WGN0
ICP
-WGN1
AQ330347384398en-000201 / 139Z8096 | 95
Specifications
D9
connector
Need help?
Do you have a question about the iC7-60EA3N05-206A and is the answer not in the manual?
Questions and answers