Cable Requirements - Danfoss iC7-60EA3N05-206A Operating Manual

Automation air-cooled enclosed drives
Table of Contents

Advertisement

iC7-Automation Air-cooled Enclosed Drives
Operating Guide
ELECTRICAL SHOCK HAZARD - LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to connect the drive properly to protective earth (PE) can result in death or serious in-
jury.
-
Ensure reinforced protective earthing conductor according to IEC 60364-5-54 cl. 543.7 or according to local safety regula-
tions for high touch current equipment. The reinforced protective earthing of the drive can be done with:
-
a PE conductor with a cross-section of at least 10 mm
-
an extra PE conductor of the same cross-sectional area as the original PE conductor as specified by IEC 60364-5-54 with a
minimum cross-sectional area of 2.5 mm
-
a PE conductor completely enclosed with an enclosure or otherwise protected throughout its length against mechanical
damage.
-
a PE conductor part of a multi-conductor power cable with a minimum PE conductor cross-section of 2.5 mm
(permanently connected or pluggable by an industrial connector. The multi-conductor power cable shall be installed with an
appropriate strain relief).
-
NOTE: In IEC/EN 60364-5-54 cl. 543.7 and some application standards (for example IEC/EN 60204-1), the limit for requiring
reinforced protective earthing conductor is 10 mA leakage current.

6.4 Cable Requirements

Follow these requirements for the mains and motor cables used in the drive system.
Select and install mains cables and motor cables according to the local safety regulations, the input voltage, and the load cur-
rent of the drive.
Use motor cables rated for +90 °C for IEC, +75 °C (167 °F) for UL. Consider the operating temperature of the mains terminals, and
make sure that the mains cables do not overheat near the mains terminals.
Use symmetrical cabling with parallel power units. Each power unit must have the same number of cables with an equal cross-
section and equal length.
Maximum number of power unit cables and bolts sizes can be found in
Only use symmetrical and shielded 3-phase mains and motor cables. See
phase cable with individual shield for each phase conductor or single-core phase conductors and PE with or without shield, see
Illustration
16.
1
3
Illustration 15: Recommended Cable Types for Mains and Motor Cabling
1
PE conductor and shield
2
PE conductor
32 | Danfoss A/S © 2023.09
W A R N I N G
2
(8 AWG) Cu or 16 mm
2
(14 AWG) (mechanical protected) or 4 mm
2
3
2
(6 AWG) Al.
2
(12 AWG) (not mechanical protected).
10.5.1 General Cable Size
Illustration
15. Do not use symmetrical and shielded 3-
2
3
Shield
AQ330347384398en-000201 / 139Z8096
Electrical Installation
2
(14 AWG)
Information.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the iC7-60EA3N05-206A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents