7.6.2 Analog Outputs

The I/O and Relay Option has 1 analog output that can be configured with the software to voltage output or current output. The
table shows the specification for the analog output.
The analog output is protected in overvoltage conditions.
Table 20: Analog Output Types and Values
Parameter
Output Voltage Range
Output Current Range
Accuracy
Reaction time
Electrical fast transient (EFT)
A
[Ohm]
18000
16000
14000
12000
10000
8000
6000
4000
2000
0
0
2
4
6
B
Illustration 28: Allowed Load Resistance of Analog Output in Current Mode
A
Load resistance
B
Allowed load resistance
48 | Danfoss A/S © 2023.09
8
10
12
14
16
Value
Voltage mode ≈ 10 kΩ
Current mode ≈ 200 Ω
0.5% of full scale
0...90% step: < 1 ms
2
+15/-15 V
+32/-32 mA
2 kV
Value
0...10 V
0...20 mA
0.5% of full scale
0...90% step: <1 ms
2 kV
C
18
20
[mA]
C
Output current
Control and Option Installation
AQ330347384398en-000201 / 139Z8096