Design Guide | iC7 Series Liquid-cooled System Modules
Table 73: Power Loss for INU Modules without Options, Modulator Type 1 (continued)
Model code
Frame
iC7-60SLIN07-2500E
3xIM12L
00F_
iC7-60SLIN07-2830E
4xIM12L
00F_
iC7-60SLIN07-3050E
4xIM12L
00F_
iC7-60SLIN07-3260E
4xIM12L
00F_
iC7-60SLIN07-3500E
5xIM12L
00F_
iC7-60SLIN07-4035E
5xIM12L
00F_
iC7-60SLIN07-4400E
6xIM12L
00F_
iC7-60SLIN07-4850E
6xIM12L
00F_
iC7-60SLIN07-5300E
7xIM12L
00F_
iC7-60SLIN07-5600E
7xIM12L
00F_
iC7-60SLIN07-6100E
8xIM12L
00F_
iC7-60SLIN07-6400E
8xIM12L
00F_
1) DC fuses
Power Losses of INU Modules without Options, Voltage Class 07, Modulator Type 2 –
10.7.9
Optimized
The specifications for the values in the table
l
Inverter module
¢
525–690 V AC (640–1100 V DC)
¢
DC voltage 1025 V DC
¢
Switching frequency 2, 3, 4, or 6 kHz
¢
204
| Danfoss Drives Oy © 2024.03
Rated
System
curre
module, 2
nt
kHz switching
I
frequency
L(1/5)
[A]
Power
Power
loss to
loss
liquid
to air
[kW]
[kW]
2500
21.64
0.22
2830
23.00
0.23
3050
25.47
0.26
3260
27.95
0.28
3500
28.33
0.29
4035
34.45
0.35
4400
36.21
0.37
4850
41.45
0.42
5300
44.14
0.45
5600
47.64
0.48
6100
50.94
0.51
6400
54.45
0.55
System
System
module, 3
module, 4
kHz switching
kHz switching
frequency
frequency
Power
Power
Power
loss to
loss
loss to
liquid
to air
liquid
[kW]
[kW]
[kW]
-
-
-
28.94
0.29
-
-
-
-
-
-
-
35.75
0.36
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
System
module, 6
kHz switching
frequency
Power
Power
Power
loss
loss to
loss
to air
liquid
to air
[kW]
[kW]
[kW]
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
AJ475942178716en-000101 / 172K2848A
+AKF
(1)
X
Power
loss
to air
[kW]
0.31
0.26
0.31
0.48
0.33
0.51
0.54
0.58
0.59
0.67
0.67
0.77
Need help?