Goodrive390L Series Lift-Dedicated VFD
Fault
Fault type
code
side
Phase loss on
E14
output side
Rectifier module
E15
overheating
Inverter module
E16
overheat
E17
External fault
RS485
E18
communication
fault
Current detection
E19
fault
Motor autotuning
E20
fault
202403 (V1.0)
Possible cause
fluctuation
occurred
input R, S, T.
Phase loss output occurs to
U, V, W (or the three phases
of the load are seriously
asymmetrical).
Air duct is blocked or fan
is damaged.
Ambient temperature too
high.
Long-time
running.
SI
external
faulty
terminal action.
Improper baud rate.
Communication
fault.
Incorrect communication
address.
Communication
from strong interference.
Poor
contact
connector
of
board.
The Hall component is
damaged.
Exception
occurred
amplification circuit.
The motor capacity does
not
match
the
capacity.
Motor parameter is set
improperly.
Autotuned
parameter
settings deviate sharply
from the standard ones.
on
Check the installation wiring.
Check the output wiring.
Check the motor and cables.
Ventilate the air duct or
replace the fan.
Lower
overload
temperature.
input
Check external device input.
Set proper baud rate.
Check the communication
line
port wiring.
Set
communication address.
Change or replace the wire or
suffers
improve the anti-interference
capability.
of
the
control
Check the connector and
re-plug.
Replace the hall component.
Replace the main control
to
board.
Change the VFD model.
VFD
Set proper motor type and
nameplate parameters.
Empty the motor load and
carry out autotuning again.
Check
parameter settings.
Ensure that the frequency
Troubleshooting
Solution
the
ambient
the
proper
motor
wiring
and
113