06(0x06) Set a Single Register (Write AO value)

This function code is used to set a specific holding register to store the configuration values for the
ET-2200 series module.
[Request]
Byte
Description
00
Net ID (Station Number)
01
Function Code
02-03
AO Address
04-05
Register Value
[Response]
Byte
Description
00
Net ID (Station Number)
01
Function Code
02-03
AO Address
04-05
Register Value
[Error Response]
Byte
Description
00
Net ID (Station Number)
01
Function Code
02
Exception Code
Copyright © 2023 ICP DAS CO., Ltd. All Rights Reserved.
Size
1 Byte
1 to 247
1 Byte
0x06
Refer to Section
Table" to find the address.
2 Bytes
Byte 02 = high byte
Byte 03 = low byte
Register Value
2 Bytes
Byte 04 = high byte
Byte 05 = low byte
Size
1 Byte
1 to 247
1 Byte
0x06
The value is the same as Bytes 02-03 of the
2 Bytes
Request
The value is the same as Bytes 04-05 of the
2 Bytes
Request
Size
1 Byte
1 to 247
1 Byte
0x86
Refer to the Modbus Standard Specifications
1 Byte
for more details.
Value
6.3
or
6.4
"Modbus Register
Value
Value