ET-2200 Series Ethernet I/O Modules
Step 4-1: Configure the Pair-Connection for the ET-2260#1 (Pull Mode)
1. Click the Pair tab to display the configuration page.
2. In the Pair-Connection Setting section, choose PULL and check the box in the Enable Mode
field to enable this mode.
3. In the Remote IP... : Port fields, enter the IP address and TCP Port of the remote ET-7255
module.
4. In the IO Count field, enter the mapped quantity for DI and DO.
For example, the PULL Mode (Remote DI to Local DO) configuration:
Enter "2" in the "IO Count" field and "0" in both the Local/Remote IO Address fields. This
means
DI0
and DI1 of ET-7255 module correspond to
5. In the Local IO Address field, select "0x: Coil Output..." and enter the starting DO address.
In the Remote IO Address field, select "1x: Discrete Input.." and enter the starting DI address.
6. Choose the Modbus protocol (e.g., TCPv4) from the Network Protocol drop-down menu.
7. Click the "Submit..." button to complete the configuration.