ET-2200 Series Ethernet I/O Modules
 1xxxx: DI Address (Base 0)
Starting
Points
Address
0
1 to nDI
0x00)
32
1 to nDI
(0x20)
64
1 to nDI
(0x40)
Notes
"R": Read
 3xxxx: AI Address (Base 0)
Starting
Points
Address
16
1 to nDI
(0x10)
64
1 to nDI
(0x40)
Note:
The "DI Counter (0x10)" and "DI Frequency (0x40)" record data as a 32-bit value and are
transmitted as two 16-bit registers. Consequently, the register's address has an offset of 2, i.e.,
the address of the second channel will be at the starting address +2, and so on. You can refer to
"FAQ_How do I read DI Counter for the PETL/t(P)ET/ET-2200 Series Modules correctly"
detailed information.
Example: Reads the 6 DI Counter on the ET-2260.
[Leading 6 bytes]
Command: 01 02 00 00 00 06
100
1
(0x64)
110
1
(0x6E)
121
1
(0x79)
Notes
"R": Read
Copyright © 2023 ICP DAS CO., Ltd. All Rights Reserved.
Description
The status of all Digital Input Channels
The status of all high-latched DI
Channels
The status of all low-latched DI Channels
Description
The Digital Counter Value
The frequency Value is * 1,000. (Note: The
Client must first divide the value by 1,000.)
01 04 00 10 00 0C
Number of DI Channels
Number of DO Channels
Number of high-speed counters
Bits per
Point
1
1
1
Bits per
Point
32
32
[Request]
6 channels * 2 registers
= 12 registers
Starting Address
16
16
16
Access
Range
Type
0 = Off
R
1 = On
0 = None
R
1 = Latched
0 = None
R
1 = Latched
Access
Value
Type
0 to
R
4294967296
0 to
R
4294967296
for more
nDI
R
nDO
R
nDI
R
-159 -