The table describes the parameters contained in the "DIO Synchronization" section.
Item
Synchronous DIO (Local Mirror)
Note:
ET-2254 supports these functions when low 8-bit is DI0 to DI7 and high 8-bit is DO8 to DO15.
Level Sync (DO = DI)
Rising Active (DO = ON)
Falling Active (DO = ON)
Additional Controls
Min-Switch Time of DO
(0 to 65535 Seconds)
Auto-off Time of DO
(0 to 65535 Seconds)
Update Settings
Copyright © 2023 ICP DAS CO., Ltd. All Rights Reserved.
This parameter is used to enable the synchronization operation in
Digital Input/Output function.
This parameter is used to enable rising activation in the Digital Input
function. When the specified DI state changes from OFF to ON, the
corresponding DO will be set to ON.
This parameter is used to enable falling activation in the Digital Input
function. When the specified DI state changes from ON to OFF, the
corresponding DO will be set to ON.
This parameter is used to set the minimum switching time between
the ON and OFF states of the Digital Output. This protects some
machines from being damaged by too many ON/OFF switches in a
short time.
This parameter is used to set the auto-off time of the Digital Output.
If the Digital Output is ON, the Digital Output will be auto-off based
on the configured time value.