Modbus Register Table For Et-2217Ci - ICPDAS ET-2268 CR User Manual

Ethernet i/o modules
Table of Contents

Advertisement

ET-2200 Series Ethernet I/O Modules
6.4.2

Modbus Register Table for ET-2217CI

 3xxxx: AI Address / 4xxxx: AO Address (Base 0)
Address
30000 ~ 30007
Analog input values of channels 0 to 7
40000 ~ 40007
30100
Number of the digital input channels
40100
30110
Number of the digital output channels
40110
30120
Number of the analog input channels
40120
30130
Number of the analog output channels
40130
30151
The firmware version
40151
30180 ~ 30194
The alias name
40180 ~ 40194
40212 ~ 40219
The type codes of analog input channels 0 to 7
Ethernet host watchdog timeout value, 5 to 65535, in seconds,
40257
0 to disable.
30258
Ethernet host watchdog timeout count.
40258
30259 ~ 30260
The module name.
40259 ~ 40260
TCP disconnection timeout value, 5 to 65535, in second,
40263
0 to disable.
Module reset timeout value, 30 to 65535, in second,
40264
0 to disable. Only for Modbus TCP protocol
30512 ~ 30519
The high latched value of analog input channel 0 to 7
40512 ~ 40519
30544 ~ 30551
The low latched value of analog input channel 0 to 7
40544 ~ 40551
Copyright © 2023 ICP DAS CO., Ltd. All Rights Reserved.
Description
Attribute
R
R
R
R
R
R
R
R/W
R/W
R
R
R/W
R/W
R
R
-164 -